Website announcement: |
In 2001, the first independent intellectual property rights fully automatic washing machine, it functions more perfect than similar ...
|
Shenzhen Constant
Electronics Co.,Ltd
Tel:(+86)0755-29981535
Fax:(+86)0755-29981536
E-mail:cstmeter@163.com
Addresss:4F/A, Factory Building No.7, Tongfuyu Industrial Zone, Fuhai Street, Bao'an District, Shenzhen, China
Postal Code: 518103
Release time:2021-01-25 丨 Reading times:655
1 Response time of S command
QUESTION: why the response will be timeout when use S command operating on a new meter which ID just set to the concentrator?
REPLY: the concentrator complete S command by known routing information. There is not routing information in concentrator for a new meter, so should leave time for learning routing information by concentrator. Normally it can operate S command quickly after 3 minutes when first timeout.
2 condition of start meter reading
QUESTION: when user want to start the concentrator auto meter reading by the window of “Startup Data Collector” in AMRS2020, sometime the software return ”ROUTER ABNORMAL”, why?
REPLY: this operation needs 3 conditions, 1st is that there are meter ID in concentrator, 2nd is concentrator possess meter reading time segment, 3rd is that the time in concentrator is correct. When user meet the problem above, they can check the 3 conditions is ok or not.
3 operation interval
QUESTION: when users use the software AMRS2020 to operate in batches the relays of meters, it often return " xxx router errors" and the success rate is low. Why?
REPLY: when user operate a meter it will return the operation result, subsequently it also maybe report a event sometime. In that case, the AMRS2020 can identify the return result only, can’t identify event report. So suggest operate meters in no batches way.
LINKS:
|
Tel:0755-29981535 Fax: 0755-29981536 E-mail:zyj@cstmeter.com Welcome to inquire agent, distribution.
All rights reserved©Shenzhen Constant Electronics Co.,Ltd |